Canadian DN-5497:C1 • 06/22/2010 — Page 1 of 2
N-MPS and NFW-MPS
Conventional Series
Manual Stations
Conventional Initiating Devices
Canadian DN-5497:C1
5497cov.jpg
General
The Notifier MPS Conventional Series manual stations provide
reporting for the NFS-320C, NFS2-640, and NFS2-3030 fire
alarm control panels; NFW-MPS series manual stations provide
reporting for FireWarden series panels. These high quality, die
cast metal manual stations include screw terminal connections,
and integrated break-glass rod. The alarm contact for the man-
ual station is rated for 1A, 24VDC. The contacts are gold plated
to avoid the risk of corrosion.
The MPS Series manual stations are available as single or two-
stage for conventional systems. Models N-MPS-SC/SCC are
single-stage manual stations. Models N-MPS-2C/2CC (two-
stage models) are similar to the N-MPS-SC (single-stage mod-
els) except they contain an additional 2nd Stage normally open
key-switch. A 2nd stage key is supplied with each unit to activate
the 2nd Stage key-switch.
All models are available with screw terminal connectors and a
hex key for reset. Two-stage models also include a key-switch
and 2 keys. All conventional models mount on a single gang
box or on a single gang box with a plaster ring.
For surface mounting, use Notifier surface back-box MPS-BB
with all conventional manual stations.
Operation
The Notifier MPS Series manual stations are operated by pulling
the handle on the front of the station. To reset the manual sta-
tion, open the manual station with the hex key (provided) and
place the handle in the normal upright position. Replace the
break-glass rod, and close the manual station front cover.
The N-MPS two-stage models include a key switch which is
located above the handle. Operation of the key-switch, when
connected to a separate alarm initiating circuit, will activate the
second stage of a two-stage alarm signaling system.
To reset the second stage activation, return the key-switch to the
original position before resetting the fire alarm control panel.
Models provided with an ancillary contact for mag-lock release,
will simultaneously release the locally connected mag-lock upon
pulling the handle on the front of the manual station.
Features
Constructed of high quality die-cast metal
Highly visible red enamel finish
English and French lettering
Single action pull lever design
Optional dual action lever kit
Integrated break-glass
Hex key resettable
Screw terminal connectors
Optional ancillary contact for local mag-lock release
Single-stage and two-stage models
Key-switch activation for second stage
Surface or semi-flush mounting
All conventional models mount on a standard single-gang
electrical box or a surface metal back-box
Architectural/Engineering
Specifications
The manual station is the Notifier N-MPS series. Operating
instructions appear in English and French lettering. The unit is
constructed of high quality die cast metal and finished in red
enamel paint to be easily identified. When the handle is pulled,
the manual station initiates an immediate operation of the alarm
detection circuit. In addition, those manual stations installed in a
two-stage system are equipped with a key-switch designed to
operate the second stage alarm initiating circuit. Manual stations
shall have the option of an ancillary contact for local mag-lock
release. Manual stations are listed with Underwriters Laborato-
ries Canada (ULC). Manual stations are required to be installed
to the current Canadian Electrical Code and the current CAN/
ULC – S524 (Standard for the installation of Fire Alarm Sys-
tems) and comply with CAN/ULC-S528, (Manual Stations for
Fire Alarm Systems, Including Accessories). Manual stations
must be installed within the limits defined by the national/local
requirements. Final acceptance is subject to the local authority
having jurisdiction.
Manual stations are provided with a hex key–operated reset lock
to reset the device after the manual station has been operated
and to allow access for testing. The stations are designed so
that after an actual emergency operation the stations cannot be
restored to normal operation without the use of the supplied hex
key. The manual stations are provided with an integrated break-
glass feature.
The addition of the dual action adapter cover (MPS-LP) requires
the operator to first lift the cover and then pull the handle of the
manual station.
All conventional models mount on a single-gang box or on a sin-
gle-gang box with a plaster ring.
For surface mounting, use Notifier surface back-box MPS-BB
for conventional manual stations.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Conventional Series

Canadian DN-5497:C1 • 06/22/2010 — Page 1 of 2N-MPS and NFW-MPS Conventional SeriesManual StationsConventional Initiating DevicesCanadian DN-5497:C154

Seite 2 - Product Line Information

Notifier® is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this

Kommentare zu diesen Handbüchern

Keine Kommentare