DN-5517:B1 • 7/13/11 — Page 1 of 4
30-2056B
Infrared Flame Detector
Conventional Initiating Devices
DN-5517:B1 • I-208
General
The Pyrotector Model 30-2056B IR Flame Detector is a
compact, unitized package containing an IR detection cell,
solid state electronics and dry Form-C (SPDT) contacts for
alarm and fault conditions. The detector is engineered to
respond to the nominal 4.45 micron band of infrared radia-
tion, which is commonly known as the CO
2 spike. See Figure
1. A characteristic of burning hydrocarbons is the emission of
unusually high levels of IR radiation in this narrow portion of
the radiation spectrum. On the other hand, extraneous light
sources that are capable of triggering an alarm in other types
of fire detectors emit very low levels of radiation in this range.
By concentrating on this narrow band of the spectral range
that is highly specific to burning hydrocarbons, combined
with the use of optical filters to discriminate against most
extraneous background radiation from a variety of sources,
including hot objects, the Model 30-2056B is able to provide
a high level of reliable fire detection, while being relatively
immune to false alarm signals.
The detector is compatible with most 24-volt filtered DC four-
wire fire alarm control panels.
Features
High immunity to false alarms caused by lightning, arc
welding, x-rays and sunlight.
Compatible with standard alarm systems.
Remote test feature assures reliable response.
Explosion-proof and watertight housing for use in a variety
of applications.
Application
The Pyrotector Model 30-2056B Infrared Flame Detector is
designed for use in applications where the occurrence of
lightning or arc welding within the protected area can cause
an ultraviolet fire detector to register a false alarm. The
detector is virtually immune to actuation caused by lightning,
arc welding, and most other extraneous light sources. It is
ideally suited for use in a variety of both indoor and outdoor
applications, in nearly any ambient lighting environment,
including the full range of artificial lighting. The housing is
explosion-proof, watertight, and dust-tight, and conforms to
applicable NEMA and NEC requirements. Typical applica-
tions that can use the 30-2056B flame detector include:
Hydrocarbon processing plants.
Hazardous storage facilities.
Offshore oil platforms.
Airport facilities.
Fuel loading racks.
DETECTOR RESPONSE TIME
The response time of the detector depends on the size of the
fire, the rate of propagation, fire type, and the proximity of the
fire to the detector. The average response time to a one
square foot gasoline fire at 50 feet is less than 6 seconds.
REMOTE TESTING
The detector has a remote test feature that allows the opera-
tor to test the detection circuitry for proper function and also
check the optical integrity of the lens from a location that is
remote from the detector installation. To initiate a test, the
operator places the system in bypass and simply presses a
5517ph1.tif
5517f1b.tif
Spectral Sensitivity Range for Hydrocarbon Fires
Figure 1
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - 30-2056B

DN-5517:B1 • 7/13/11 — Page 1 of 430-2056BInfrared Flame Detector Conventional Initiating DevicesDN-5517:B1 • I-208GeneralThe Pyrotector Model 30-205

Seite 2 - Specifications

Page 2 of 4 — DN-5517:B1 • 7/13/11test switch, usually located at the control panel. This actuatesan integral IR radiation source that is mounted insi

Seite 3 - Installation

DN-5517:B1 • 7/13/11 — Page 3 of 4MaintenanceTo assure maximum detector sensitivity, the lens must bekept free of dirt or other contaminating film.The

Seite 4

Page 4 of 4 — DN-5517:B1 • 7/13/11NOTIFIER® is a registered trademark of Honeywell International Inc.©2011 by Honeywell International Inc. All rights