dn-7000:a2 • 06/17/10 — Page 1 of 2
NC-100(A)
Control Module for
FireWarden Series Panels
Addressable
dn-7000:a2 • A1-360
General
The NC-100(A) Addressable Control Module provides NOTI-
FIER’s FireWarden Series intelligent control panels a super-
vised Class B (Style Y) of Class A (Style Z) circuit for
Notification Appliances (horns, strobes, etc.). Addressability
allows the NC-100(A) to be activated, either manually or
through panel programming, on a select (zone or area of cov-
erage) basis.
Features
Built-in type identification automatically identifies these
devices to the control panel.
Internal circuitry powered directly by two-wire SLC loop.
The NC-100(A) module requires power (for horns, strobes,
etc.).
Integral LED “blinks” when communicating, and turns on
steady when activated.
High noise immunity (EMF/RFI).
The NC-100(A) may be used to switch 24-volt NAC power.
Wide viewing angle of LED.
SEMS screws with clamping plates for wiring ease.
Direct Decade entry of address: 01 – 99 with FireWarden-
100-2(C), or 01-50 with the FireWarden-50(C).
Applications
The NC-100(A) is used to switch 24 VDC audible/visual power.
Construction
The face plate is made of off-white heat-resistant plastic.
Controls include two rotary switches for direct-dial entry of
address setting.
The NC-100(A) is configured for a single Class B (Style Y)
or Class A (Style Z) Notification Appliance Circuit.
Operation
Each NC-100(A) uses one of the module addresses on a SLC
loop. It responds to regular polls from the control panel and
reports its type and status, including the open/normal/short
status of its Notification Appliance Circuit (NAC). The LED
blinks with each poll received. On command, it activates its
internal relay. The NC-100(A) supervises Class B (Style Y) or
Class A (Style Z) notification or control circuits.
Upon code command from the panel, the NC-100(A) will dis-
connect the supervision and connect the external power sup-
ply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication
to the panel that the control relay actually turned ON. The
external power supply is always relay-isolated from the com-
munication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the con-
trol panel.
Specifications
Normal operating voltage: 15 to 32 VDC.
Maximum SLC current draw: 6.5 mA (LED on).
Average operating current: 350 μA (LED flashing).
External supply voltage: maximum 80 volts (RMS or DC).
Drain on external supply: 2 mA maximum (using internal
EOL relay).
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
•FM approved
UL/ULC Listed: file S635.
CSFM approved: file 7300-0028:230.
MEA approved: file 72-01-E Vol. 2.
NC-100(A)
7000cov.JPG
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - NC-100(A)

dn-7000:a2 • 06/17/10 — Page 1 of 2NC-100(A)Control Module for FireWarden Series PanelsAddressabledn-7000:a2 • A1-360GeneralThe NC-100(A) Addressable

Seite 2 - Product Line Information

Page 2 of 2 — dn-7000:a2 • 06/17/10NOTIFIER® is a registered trademark of Honeywell International Inc. ©2010 by Honeywell International Inc. All right

Kommentare zu diesen Handbüchern

Keine Kommentare