DN-6935:D • 12/08/2011 — Page 1 of 2
FSP-851(A) Series
Intelligent Plug-In Photoelectric
Smoke Detectors with FlashScan®
Intelligent/Addressable Devices
DN-6935:D • H-202
General
Notifier FSP-851(A) Series intelligent plug-in smoke detectors
with integral communication provide features that surpass con-
ventional detectors. Detector se
nsitivity can be programmed in
the control panel software. Sensitivity is continuously monitored
and reported to the panel. Point ID capability allows each detec-
tor’s address to be set with rotary, decimal address switches,
pro
viding exact detector location for selective maintenance
when chamber contamination reaches an unacceptable level.
The FSP-851(A) photoelectric detector’s unique optical sensing
chamber is engineered to sense smoke produced by a wide
range of combustion sources. Dual electronic thermistors add
135°F (57°C) fixed-temperature thermal sensing on the FSP-
851T(A). The FSP-851R(A) is a remote test capable detector for
use with DNR(A)/DNRW duct detector housings. FSP-851(A)
series detectors are compatible with Notifier Onyx and CLIP
series Fire Alarm Control Panels (FACPs).
FlashSca
(U.S. Patent 5,539,389) is a communication proto-
col developed by Notifier that greatly increases the speed of
comm
unication between analog intelligent devices. Intelligent
devices communicate in a grouped fashion. If one of the devices
in the group has new information, the panel’s CPU stops the
group poll and concentrates on single points. The net effect is
response speed greater than five times that of earlier designs.
Features
Sleek, low-profile design.
Addressable-analog communication.
Stable communication technique with noise immunity.
Low standby current.
Two-wire SLC connection.
Compatible with FlashScan® and CLIP protocol systems.
Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on
Flash
Scan systems).
Optional remote, single-gang LED accessory.
Dual LED design provides 360° viewing angle.
Visible bi-color LEDs blink green every time the detector is
ad
dressed, and illuminate steady red on alarm (FlashScan
systems only).
Remote test feature from the panel.
Walk test with address display (an address on 121 will blink
the detector LED:
12-[pause]-1(FlashScan systems only).
Built-in functional test switch a
ctivated by external magnet.
Built-in tamper-resistan
t feature.
Sealed against back pressure.
Constructed of off-white fire-resistant plastic, designed to
comme
rcial standards, and offers an attractive appearance.
94-5V plastic flammability rating.
SEMS screws for wiring of the separate base.
Optional relay, isolator, and sounder bases.
Specifications
Sensitivity: 0.5% to 2.35% per foot obscuration
Size: 2.1"
(5.3 cm) high; base determines diameter.
B210LP(A): 6.1
" (15.5 cm) diameter.
B501(A): 4.1" (10.4 cm)
diameter.
B200S(A): 6.875" (17.46
cm) diameter.
B200SR(A):
6.875" (17.46 cm) diameter.
B224RB(A): 6
.2" (15.748 cm) diameter.
B224BI(A): 6.2"
(15.748 cm) diameter.
Shipping Weight: 5.2oz. (1
47g).
Operating Temperature range: FSP-851
(A), 0°C to 49°C
(32°F to 120°F). FSP-851T(A), 0°C to 38°C (32°F to 100°F).
Low temperature signal for FSP-851T(A) at 45°F +/- 10°F
(7.22°C +/- 5.54°C). FSP-851R(A) installed in a DNR(A)/DNRW,
-20°C to 70°C (-4°F to 158°F).
UL/ULC Listed Velocity Range: 0-400
0 ft/min. (1219.2 m/
min.), suitable for installation in ducts.
Relative Humidity: 10%
-93% noncondensing.
Thermal Ratings: Fi
xed-temperature setpoint 135°F (57°C).
DETECTOR SPACING AND APPLICATIONS
FSP-851(A) in B210LP(A) Base
B210-2951.jpg
Notifier recommends spacing detectors in compliance with
NFPA 72. In low airflow applications with smooth ceiling, space
detectors 30 feet (9.144m) for ceiling heights 10 feet (3.148m)
and higher. For specific information regarding detector spacing,
placement, and special applications refer to NFPA 72. System
Smoke Detector Application Guide, document A05-1003, is
available at systemsensor.com
ELECTRICAL SPECIFICATIONS
Voltage Range: 15-32 volts DC peak.
Standby Current (max. avg.): 30
0μA @ 24VDC (one commu-
nication every five seconds with LED enabled).
LED Current (max.): 6
.5mA @ 24 VDC (“ON”).
Installation
FSP-851(A) plug-in detectors use a separate base to simplify
installation, service, and maintenance. A special tool allows
maintenance personnel to plug in and remove detectors without
using a ladder.
Mount base (all base types) on an electrical backbox which is at
le
ast 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
NOTE: 1) Because of inherent supervision provided by the SLC
loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult the ISO-X(A) installation
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - FSP-851(A) Series

DN-6935:D • 12/08/2011 — Page 1 of 2FSP-851(A) SeriesIntelligent Plug-In PhotoelectricSmoke Detectors with FlashScan®Intelligent/Addressable DevicesD

Seite 2 - Product Line Information

Page 2 of 2 — DN-6935:D • 12/08/2011-Notifier® and FlashScan® are registered trademarks of Honeywell International Inc.©2011 by Honeywell Internation

Verwandte Modelle: FSP-851T | FSP-851 |

Kommentare zu diesen Handbüchern

Keine Kommentare