dn-4867:b • 03/27/09 — Page 1 of 4
UDACT
Universal Digital Alarm
Communicator Transmitter
Annunciator Control Systems
dn-4867:b • D-160
General
The Universal Digital Alarm Communicator Transmitter
(UDACT) is designed for use on the Notifier NFS-320, NFS2-
640, NFS2-3030, NFS-640 and NFS-3030 Fire Alarm Control
Panels and on the NCA-2 and NCA Network Control Annunci-
ator. When used in conjunction with the NCA-2 network con-
trol annunciators the UDACT can report the status of all control
panels on NOTI•FIRE•NET™. The UDACT transmits system
status to UL listed Central Station Receivers via the public
switched telephone network.
NOTE: The UDACT can also be used with legacy panels. Please
refer to the UDACT manual for more information.
The UDACT is compact in size and may be mounted externally
in a separate cabinet. EIA-485 annunciator communications
bus and regulated 24-volt connections are required.
The UDACT is capable of transmitting the status of software
zones (Alarm and Trouble), System Trouble, Panel Off-Normal,
Supervisory, Bell Trouble, Low Battery, and AC Fail. The
UDACT is capable of transmitting all of the zone and point sta-
tus associated with each panel.
When the UDACT is used with the , NFS-3030, NFS2-3030,
and NCA-2 it is capable of reporting up to 2,040 points.
Reporting may be in the form of points or zones (refer to the
UDACT manual for specific reporting parameters). The first
568 points transmitted may be programmed for a variety of
types, including fire, waterflow, supervisory, etc. Remaining
points transmitted are for fire alarm only.
NOTE: Descriptions regarding point capacity, listed above, are for
receivers which receive in Ademco Contact ID format. See chart
on page 2 for compatible receivers.
Features
Maximum of 14 point trouble messages transmitted per
hour.
Dual phone lines.
Dual telephone line voltage detect.
Surface Mount Technology.
Compact in size: 6.75" x 4.25" (17.145 x 10.795 cm).
Built-in programmer.
Built-in 4-character red 7-segment LED display.
Manual Test Report function.
Manual Transmission Clear function.
Mounts in a separate enclosure (ABS-8RB or UBS-1).
Communicates vital system status including:
Independent zone fire alarm.
Independent zone non-fire alarm.
Independent zone trouble.
Independent zone supervisory.
AC (mains) Power Loss (programmable).
Low Battery and Earth Fault.
System Off-Normal.
12 or 24 hour test signal.
Abnormal Test Signal per new UL requirements.
EIA-485 Communication Bus Failure.
Annunciation of UDACT Troubles including: loss of phone
lines, communication failure with either Central Station, total
communications failure.
Troubleshoot Mode converts keypad to DTMF touchpad.
Individual LEDs for: Power, EIA-485 Loss, Manual Test,
Kissoff, Comm Fail, Primary Line Seize, Secondary Line
Seize and Modem Communications.
Open Collector relay driver for Total Communications Fail-
ure or UDACT trouble.
Real-time clock.
Extensive transient protection.
Simple EIA-485 interface to host panel.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL Listed: S635
ULC Listed: CS100 Vol. VII
MEA: 328-94-E; 317-01-E3
CSFM: 7300-0028:174; 7165-0028:214; 7165-0028:224;
7170-0228:216; 7170-0028:223; 7165-0028:243, 7170-
0028:244
INDUSTRY CANADA: 2132 6030 A
FCC: 1W6-USA-20723-AL-E
FM Approved
Communication Formats
3+1 Standard • 4+1 Standard • 4+2 Standard
4+1 and 4+2 Ademco Express • Ademco Contact ID
UDACT
4867udac.wmf
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Communicator Transmitter

dn-4867:b • 03/27/09 — Page 1 of 4UDACTUniversal Digital AlarmCommunicator TransmitterAnnunciator Control Systemsdn-4867:b • D-160GeneralThe Universal

Seite 2 - Ordering Information

Page 2 of 4 — dn-4867:b • 03/27/09NOTE: Ademco Contact ID must be used for independent zonereporting.Type Mode FeatureAdemco Contact ID format only)

Seite 3

dn-4867:b • 03/27/09 — Page 3 of 4Format # (Addresses 16 & 42)Ademco 685 (1)Silent Knight 9000ITI CS-4000 (3)FBI CP220FBOsborne Hoffman Models 1 &

Seite 4

Page 4 of 4 — dn-4867:b • 03/27/09NOTI•FIRE•NET™ is a trademark and Notifier® is a registered trademark ofHoneywell International Inc.©2006 by Honeywe